This template is used to control a relatively complex four-pipe air conditioning unit with return or exhaust fan. It uses heating valve for heating in winter and cooling valve for cooling in summer. Outside Air Damper Control generates outputs based on preset values, while Heating/Cooling Valve Control generates outputs based on return air temperature, temperature setpoint and PID calculation. Fault Alarm Protection includes individual sensor fault alarms, filter differential pressure switch and low limit temperature switch.
Legend | Description | Legend | Description |
---|---|---|---|
OAT | Outside Air Temperature | EF | Exhaust Fan |
EAD | Exhaust Air Damper | SF | Supply Fan |
MAD | Mix Air Damper | SAT | Supply Air Temperature |
OAD | Outside Air Damper | SAH | Supply Air Humidity |
PFILT | Primary Filter | SAP | Supply Air Pressure |
SFILT | Secondary Filter | RAT | Return Air Temperature |
HV | Heating Valve | RAH | Return Air Humidity |
CV | Cooling Valve | RACO2 | Return Air CO2 |
HUM | Humidifier | R | Room |