Right-click on an EM BUS port on the controller to configure the I/O module communication parameters. See the following table:

Parameter

Description

BaudRate

EM bus port communication rate

ResponseTime(ms)

Response timeout in milliseconds

RetryCount

Number of retries before a communication error is marked

LiveCycleTime(s)

The lifetime of the module in seconds

EnbTermRes

Enables or disables line resistance

On the corresponding I/O module, right-click on the EM BUS port to configure the module address (1...31). The controller supports to connect to max. five I/O extension modules. It is recommended to set the five modules to addresses 1 (20), 2 (21), 4 (22), 8 (23) and 16 (24) respectively.