I/O extension module BSP LED status indication:

State

Meaning

Green ON

BSP running

Red flashing at 2 Hz

BSP error (software error)

Flashing between red and green, per second

BSP upgrade mode

Red ON

Hardware error

BUS LED indicates the controller’s communications state. BUS LED states:

State

Meaning

Green ON

Communication running, I/O working

Orange ON

Communications active, but parameter not configured successfully

Red ON

Communication error