The edge controller communicates with Desigo Plug and Play Automation cloud app and supports functions such as DNS and NTP, as detailed below.
Traffic types, services and ports
Service | Protocol | Transport | Port | Remark |
|---|---|---|---|---|
|
Local access | http | TCP | 80 |
|
Cloud access | https | TCP | 443 |
|
Link-Local Multicast Name Resolution | llmnr | TCP | 5355 | Optional |
Domain name resolution | dns | UDP | 53 |
|
Network time | ntpv4 | UDP | 123 |
|
Local access, for troubleshooting only | ssh | TCP | 22 | Disabled by default and must be deactivated during normal operation |
Endpoints
Service | URL | Port |
|---|---|---|
|
Authentication Proxy | proxy.connectivity-product-int.siemens.com | 443 |
Bootstrap | bootstrap.connectivity-product-int.siemens.com | 443 |
Firmware update service | ota-update.connectivity-product-int.siemens.com | 443 |
MQTT | mqtt.connectivity-product-int.siemens.com | 443 |
NTP | 0.siemens.pool.ntp.org | 123 |