Description | Possible cause | Solution |
|---|---|---|
A device has been selected in the “Devices” section but no channels are displayed in the “Channels” section. | The device that has been selected is not compatible with the device to which the source channel (“Source” section) belongs. A channel of the selected device can therefore not be selected as the destination channel and is therefore not displayed in the “Channels” section. | Select a device that is compatible with the set source channel. Compatible devices |
While loading a channel assignment, the following error message appears: “The channel (1.2.34 – X) is disabled, please enable all used channels first.” | A channel that is used in the channel assignment is disabled. | Re-enable the channel mentioned in the error message in the Device Settings of the device. |
While importing source channel settings, the following error message appears: “The imported data is not compatible with the selected application.” | The source channel that has been selected and is displayed in the “Source” section is not compatible with the source channel whose settings are imported. | Select the source channel that is compatible with the source channel whose settings are to be imported. Or: In the settings for the import, select the import file of the channel that is compatible with the selected source channel. |
While importing source channel settings, the following error message appears: “The assignment of the group address has failed: Group address 'x/y/z New group address' could not be connected to the communication object ’<number and name of the communication object>'. Different object size.” | The group addresses are connected to data types that are not compatible with the selected source channel. | Repeat the import of the source channel settings without the “Copy group” option. |
While loading a saved channel assignment, the following error message appears: “Load error – Load channel selection error: at least one device was not found.” | At least one device that is included in the channel assignment was deleted from the ETS project beforehand. | If a backup of the project was created prior to deleting the devices, use the backup copy of the project. If no backup is available, create the channel assignment again. |
During copying, an error appears stating that the versions of the devices are not compatible. | One or more devices of the loaded channel assignment have been updated in the meantime. Version V1 are not compatible with V3. | Create the channel assignment anew using devices of version V3. |