Mechanical adaption / connect to controller

To commissioning SSA911.02TH, see Product documentation.

  • The actuator stem on the wireless radiator valve actuator SSA911.02TH is fully retracted.
  1. Install the wireless radiator valve actuator on the radiator.
  1. Prepare control as per product documentation.
  1. Scan the DataMatrix code on the wireless radiator valve actuator.
  • The system assigns the actuator.
  1. Remove the insulation strip from the battery compartment or install the batteries.
  • The actuator mechanically adapts to the radiator valve (takes ca. 10-15 seconds).
  • Connects automatically.
  • PA displays. The wireless symbol flashes.
  • It takes up to 1 hour until the radiator actuator valve is paired and operational.
  • In the event of an error message on the display remove the batteries and reinstall to restart the device.
  • Commissioning is completed.