You can either tag a single data point or batch tag the data points in Desigo Optic. Both options are described below.
Single data point
- You have saved the tag from the Point Filter.
- The Desigo Optic tool is open.
- Go to your Project.
- Select the required data point.
- Add the tag from the Point Filter.
The data point must be activated in Building X. This is similar to data points from other sources and described in the following chapter: Activating data points
Batch tagging data points
- You have saved the tag from the Point Filter.
- The Desigo Optic tool is open.
- Go to Advanced Apps > Folio.
- Use the search bar to filter specific points.
- The Points filter criteria returns all data points.
- Select the required data points. If all data points should be included, select the checkbox on top.
- Go to Edit on top of the right side.
- The Edit dialog opens.
- Select + Add to add the tag from the Point Filter.
- Select Apply.
Determining the writing level of synched points
In some cases you may want to specify the priority level at which a writable synchronized point within Building X writes to Desigo Optic.
- You have saved the tag from the Point Filter.
- The Desigo Optic tool is open.
- Go to your Project.
- Select the required data point.
- Add the tag
bxCCWriteLevel
followed by a colon “:” and a level number between 1-17 (the default is 8). For example:bxCCWriteLevel:13
.
- If the point is commanded through Building X, that value will be updated in Optic at the specified priority level.