• The Devices app with the Information tab of the added device is open in another browser tab.
  1. Go to the Connect Box web interface.
  1. Go to Connect Boxes and select your device.
  1. Go to Configuration > Gateways.
  1. Select Create new gateway.
  1. Enter a Name for the new gateway.
  1. (Optional) Enter the Description.
  1. From the Protocol dropdown list, select MQTT Gateway.
  1. Copy and paste the following values from the Devices app to the Connect Box web interface:
  • In the Server host field, paste the Server address.
  • Remove the last three digits after the *:* from the Server address and paste them to the Server port.
  • In the Client ID field, paste the Client ID.
  • In the Uplink topic format field, paste the uplink.
  • In the Downlink topic field, paste the downlink.
  1. Select the latest version from the MQTT version dropdown list.
  1. Select the TLS certificate checkbox (1).
  • The options to upload the certificates display.
  1. In the Devices app, select Download to download the keys.
  • The Credentials.zip file is saved to your local hard drive in the Downloads folder.
  1. Copy the files from credentials.zip file into your own folder.
  • client.crt.
  • private.key
  • rootCA.crt
1234
  1. Select CA Certificate (2), then complete the following steps:
  • Select You can upload a file clicking here.
  • Select Choose a file... and select rootCA.crt file from your local hard drive.
  • For File type select MQTT CA Certificate.
  • For File visibility select Connect Box or Connect Box On Premise from the dropdown list.
  • For Connect Box or Connect Box on Premise select your device.
  1. Select Save.
  1. Upload the client.crt file as Client Certificate (3) and private.key file as Private Key (4) the same way. Make sure to select the correct File type for each file.
  1. Select Save.
  1. Open the Properties of your Connect Box.
  1. Select Add Property.
  1. Select the data points to assign them to the MQTT Gateway.
  1. Select Save, then select Save changes.
  1. Select Send to the box to make the data points available in Building X.
  • The Connect Box device is fully configured and synchronized with the Connect Box web interface.
  1. In the Devices app, select Synchronize and wait approximately 10 seconds.
  1. After the synchronization is finished, refresh the browser.
  1. Check the Connection state for Online state display.
  • The Connect Box device is online and synchronized.
  • The data points can be viewed in the Data Setup app (Data points).