Add the gateway to Fire Panel configuration
- The Engineering tool is open.
- Open the site configuration.
- For Type select FG2004.
- Select Ethernet station.
- Select Add.
Adding site-wide visibility
- The Engineering tool is open.
- Select Operation in the upper right corner to open the operations tree.
- Open the dropdown tree Station > PMI.
- Perform a right click on Standard visibility.
- Select Assign.
- The Assign dialog opens.
- Select Site > Site > Assign.
- Select Close.
- Open the dropdown tree Site > Global system configuration.
- Select Global behaviour.
- The Global behaviour card opens.
- In Cloud select the respective boxes to transfer the data into the cloud and enable commands.
Setting a time master
The gateway can act as a time master for all fire panels in the network with IP8. This feature is not supported with IP7.
- The Engineering tool is open.
- Select Operation in the upper right corner to open the operations tree.
- Open the dropdown tree Site > Global system configuration.
- Perform a right click on Global system time.
- Select Unassign.
- Perform a right click on Global system time.
- Select Assign.
- The New effect dialog opens.
- Select the FG2004 > Assign > Close.
Completing the setup
- The Engineering tool is open.
- Select Network in the upper right corner to open the network tree.
- Open the dropdown tree Global system configuration > Network configuration > Ethernet sub-net.
- Perform a right click on Functions.
- Select Assign.
- The Assign dialog opens.
- Select the function GAP.
- Select the Cerberus PRO panel.
- Select Assign > Close.
- Select the newly assigned GAP.
Setting up a route to the gateway
- The Engineering tool is open.
- Select Network in the upper right corner to open the network tree.
- Open the dropdown tree Global system configuration > Network configuration > Ethernet sub-net.
- Perform a right click on Routes.
- Select New > Route.
- The Route card opens.
- Enter the IP address of the cloud gateway in the Destination address field.
The IP address of each panel can be found in the Ethernet sub-net > Connections in the table on the right side.
Initializing the gateway
- The Engineering tool is open.
- Change the IP address of the local ethernet interface of your computer to 192.168.200.5.
- Select the FG2004.
- In the navigation bar, select Commissioning > Initialize station.
- Select Start in the Initialize station dialog.
- After the installation, in the navigation bar select Commissioning > Download site.