1. Select the device to connect to the Cloud.
  1. Select the AS tab.
  1. Do the following:
  • for the device version ≤ 1.5: select the Cloud tab.
  • for the device version ≥ 1.6: select LAN > IPv4 > and then the Cloud port tab.
  1. Select Enable Cloud.
  1. Enter the other parameters for the connection.

Settings

Description

Enable Cloud

Select the BACnet property Enable connectivity to enable the Cloud port.

Enable BACnet tunnel

Select the BACnet property Enable BACnet tunnel to enable BACnet tunneling.

Reconnect delay

Enter the delay time to reconnect in seconds.
Default: 300. Range: 30…86400 sec

Retries

Enter the numbered of retries to connect to a Cloud object if the connection is lost.
Default: 10. Range: 1…100 sec

Network Number

Read only. BACnet property that displays the BACnet network number.
Default: 55489

Registration URI

Read only. BACnet property that includes the Cloud registration URI. The Cloud agent uses it to register the device in the Cloud.

Activation key

The key is visible after initial readback.