Single-speed fan 11 - Application Guide - DXR1.E09PDZ-113 - DXR1.E10PL-113 - DXR1.M09PDZ-113
Fan powered box with reheater DXR1.. room automation stations Application Guide
- Product Family
- Desigo TRA
- Desigo
- Content Language
- English
- Content Type
- Technical Documentation > Application
- Document No
- A6V13959502_en--_a
- Download ID
- A6V13959502
- Stock No.
- S55499-D459
- S55499-D463
- S55499-D457
- Product No.
- DXR1.E09PDZ-113
- DXR1.E10PL-113
- DXR1.M09PDZ-113
- Access level
- Internet
- File Type
- html
Single-speed fan 11- Set Fan support for VAV box (mandatory). For use with FPB (fan powered box), the configurable value must match the box type:
- No for fan coil unit or heat pump (not used for DXR1 application)
- On request for parallel fan powered VAV box
- Continuous on for series fan powered VAV box

- Enable state input (optional). Set it to 1:Yes when a binary fan status input is used, otherwise set it to 0:No.


- Temperature control sequence for heating and cooling is as follows: