Fixed parameters as below.
Setpoint shift value range adjustment
The setpoint adjustment range can be changed on Room unit QMX1.M34H. Change three values as a pair: Present minimum value, Present maximum value and Present value.
Note:
- Setpoint range adjustment function is available with: a) Firmware version of DXR1 is 54.7.9 or higher; b) QMX1.M34H (production date later than April 1st, 2020).
- Maximum adjusted range is -10…10 K.
Following is an example of changing maximum adjusted range to -5…5 K.