Room HVAC coordination - Application Guide - DXR1.E09PDZ-113 - DXR1.E10PL-113 - DXR1.M09PDZ-113

Fan powered box with reheater DXR1.. room automation stations Application Guide

Product Family
Desigo TRA
Desigo
Content Language
English
Content Type
Technical Documentation > Application
Document No
A6V13959502_en--_a
Download ID
A6V13959502
Stock No.
S55499-D459
S55499-D463
S55499-D457
Product No.
DXR1.E09PDZ-113
DXR1.E10PL-113
DXR1.M09PDZ-113
Access level
Internet
File Type
html
md
  • Introduction
  • Compatible variants
  • Application configuration
  • On-board output
  • On-board input
  • Room unit
  • Accessories
  • KNX PL-Link device
  • HVAC
  • Supply air VAV
  • Heating coil
  • Room HVAC coordination
  • Plant mode determination
  • Rapid ventilation operation
  • Room temperature setpoint determination
  • Temperature control for cooling
  • Temperature control for heating
  • Heating/cooling state determination
  • Ventilation control
  • Green leaf
  • Room coordination
  • Room operating mode determination
  • Room green leaf
  • Room operator unit interface
  • Parameter setting
  • On-board output
  • Supply air VAV position
  • Angle adaption
  • Control action
  • Auto position synchronization
  • Heating coil valve position – Electric 1-stage
  • How to configure parameters if message “See “Default values” task for a complete list of configuration parameters” appears
  • On-board input
  • Supply air VAV differential pressure
  • Room unit
  • Accessories – Compatible with DXR1.E09PxZ-11x \ DXR1.M09PxZ-11x only
  • KNX PL-Link device - Room operator unit device 1 – Compatible with DXR1.E10PL-11x only
  • HVAC
  • Supply air VAV
  • Supply air VAV 12, press, duct area, ctr.
  • Supply air VAV 13, press, flow conv, ctr.
  • Fan
  • Single-speed fan 11
  • Heating coil
  • Electric heating coil 13, 1 binary outp.
  • Room HVAC coordination
  • Temperature control for cooling
  • Temperature control for heating
  • Ventilation control
  • NOTE: Heating\cooling temperature control changeover operation
  • Room coordination
  • Room operating mode determination
Room HVAC coordination

Back to home page