Wireless room sensors (WRS), available in versions measuring temperature only, temperature and relative humidity, or temperature, relative humidity and air quality (CO2), extend the operational range of the wireless room actuators. The interworking requires the function Calculate effective room temperature.
.
The average temperatures measured by the WRS in a room are sent to the WRA devices. This value is not visible in the detail cards. The WRS also allows specifying a numeric correction for the quantities it measures. The devices are supported by OTA updates.
Humidity and air quality measurements do not trigger any event but the data can be read in the respective device detail card.
Note: A Thread border router must be commissioned before any wireless room sensor can be commissioned.
- A Thread border router or mesh extender of which the WRS is in coverage has been installed and is powered on.
- Go to Scan and assign and choose WRS device to commission by selecting its Assign button. Please note that the status of the device must be as described under Before you start. Click Next to continue.
- Click Scan and direct the scanner onto the QR code on the product.
- Select Thread border router to assign the device to from the drop-down menu.
- The Thread device is automatically onboarded. Confirm by clicking Save and then Next.
- The Thread device is automatically configured and is ready to use.