- Select assigned device and click Next to start commissioning.
- Click Next and direct the scanner onto the bar code on the product. The bar code can also be entered manually in the designated field.
- When the code has been registered, a confirmation message is shown. Click Save to continue.
- Successful commissioning is indicated by a message that the meter is online.
- The heat/cooling meter is commissioned.
NOTICE
Heat/Cool meter commissioning failing
The meter is connected using its M-Bus secondary address, an 8-digit code which by default corresponds to the serial number in the barcode on the device. If the M-Bus secondary address has been changed, commissioning using the serial number will fail. Please ensure that the number used for commissioning is the same as M-Bus secondary address on the device. If necessary, add initial zeros so that the code has 8 digits.