The setpoint scheduler is used to set individual room temperatures used by the Desigo Plug and Play Automation app. It is represented on a calendar where schedules can be set and recurring on a daily or weekly basis.
- The setpoint scheduler has been added to the system, assigned to one or more rooms, and deployed.
- In Commissioning > Functions, open the setpoint calendar with Edit.
- Select Edit again to unlock the scheduler.
- Select a day of the week and a time to create a new setpoint. Adjust the setpoint temperature by typing or using the slider.
- Change the activation time of the setpoint by sliding it up or down.
- To copy a daily schedule to another day, select Copy. Mark the day to copy the schedule to, select Paste and save.
- The setpoint scheduler is updated.
Note: The default setting is applied at midnight as a fixed switching point.