类型 | 变量命名 | 中文描述 | 英文描述 | 中文单位 | 英文单位 | ||
---|---|---|---|---|---|---|---|
状态0 | 状态1 | State 0 | State 1 | ||||
DI | ET_LLL | 膨胀水箱超低液位 | Expansion Tank Low-low Level Status | 关 | 开 | OFF | ON |
DI | ET_LL | 膨胀水箱低液位 | Expansion Tank Low Level Status | 关 | 开 | OFF | ON |
DI | ET_HL | 膨胀水箱高液位 | Expansion Tank High Level Status | 关 | 开 | OFF | ON |
DI | ET_HHL | 膨胀水箱超高液位 | Expansion Tank High-high Level Status | 关 | 开 | OFF | ON |
DI | SM_LLL | 污水坑超低液位 | Sump Low-low Level Status | 关 | 开 | OFF | ON |
DI | SM_LL | 污水坑低液位 | Sump Low Level Status | 关 | 开 | OFF | ON |
DI | SM_HL | 污水坑高液位 | Sump High Level Status | 关 | 开 | OFF | ON |
DI | SM_HHL | 污水坑超高液位 | Sump High-high Level Status | 关 | 开 | OFF | ON |
|
|
|
|
|
|
|
|
DI | DWT_LLL | 生活水箱超低液位 | Domestic Water TankLow-low Level Status | 关 | 开 | OFF | ON |
DI | DWT_LL | 生活水箱低液位 | Domestic Water TankLow Level Status | 关 | 开 | OFF | ON |
DI | DWT_HL | 生活水箱高液位 | Domestic Water TankHigh Level Status | 关 | 开 | OFF | ON |
DI | DWT_HHL | 生活水箱超高液位 | Domestic Water TankHigh-high Level Status | 关 | 开 | OFF | ON |
DI | MT_LLL | 补水箱超低液位 | Makeup Tank Low-low Level Status | 关 | 开 | OFF | ON |
DI | MT_LL | 补水箱低液位 | Makeup Tank Low Level Status | 关 | 开 | OFF | ON |
DI | MT_HL | 补水箱高液位 | Makeup Tank High Level Status | 关 | 开 | OFF | ON |
DI | MT_HHL | 补水箱超高液位 | Makeup Tank High-high Level Status | 关 | 开 | OFF | ON |
DI | SWT_LLL | 软化水箱超低液位 | Soft Water Tank Low-low Level Status | 关 | 开 | OFF | ON |
DI | SWT_LL | 软化水箱低液位 | Soft Water Tank Level Status | 关 | 开 | OFF | ON |
DI | SWT_HL | 软化水箱高液位 | Soft Water Tank High Level Status | 关 | 开 | OFF | ON |
DI | SWT_HHL | 软化水箱超高液位 | Soft Water Tank High-high Level Status | 关 | 开 | OFF | ON |
DI | PMP_STA | 水泵运行状态 | Pump Status | 关 | 开 | OFF | ON |
DI | PMP_FA | 水泵故障报警 | Pump Fault Alarm | 正常 | 报警 | OK | FLT |
DI | PMP_MA | 水泵手自动状态 | Pump Auto/Manual Select | 手动 | 自动 | MAN | AUTO |
DO | PMP_CMD | 水泵启停命令 | Pump Command | 关 | 开 | OFF | ON |
DI | SMP_STA | 污水泵运行状态 | Sump Pump Status | 关 | 开 | OFF | ON |
DI | SMP_FA | 污水泵故障报警 | Sump Pump Fault Alarm | 正常 | 报警 | OK | FLT |
DI | SMP_MA | 污水泵手自动状态 | Sump Pump Auto/Manual Select | 手动 | 自动 | MAN | AUTO |
DO | SMP_CMD | 污水泵启停命令 | Sump Pump Command | 关 | 开 | OFF | ON |
DI | DWP_STA | 生活水泵运行状态 | Domestic Water Pump Status | 关 | 开 | OFF | ON |
DI | DWP_FA | 生活水泵故障报警 | Domestic Water Pump Fault Alarm | 正常 | 报警 | OK | FLT |
DI | DWP_MA | 生活水泵手自动状态 | Domestic Water Pump Auto/Manual Select | 手动 | 自动 | MAN | AUTO |
DO | DWP_CMD | 生活水泵启停命令 | Domestic Water Pump Command | 关 | 开 | OFF | ON |
DI | MP_STA | 补水泵运行状态 | Makeup Pump Status | 关 | 开 | OFF | ON |
DI | MP_FA | 补水泵故障报警 | Makeup Pump Fault Alarm | 正常 | 报警 | OK | FLT |
DI | MP_MA | 补水泵手自动状态 | Makeup Pump Auto/Manual Select | 手动 | 自动 | MAN | AUTO |
DO | MP_CMD | 补水泵启停命令 | Makeup Pump Command | 关 | 开 | OFF | ON |
|
|
|
|
|
|
|
|
DI | SWP_STA | 软化水泵运行状态 | Soft Water Pump Status | 关 | 开 | OFF | ON |
DI | SWP_FA | 软化水泵故障报警 | Soft Water Pump Fault Alarm | 正常 | 报警 | OK | FLT |
DI | SWP_MA | 软化水泵手自动状态 | Soft Water Pump Auto/Manual Select | 手动 | 自动 | MAN | AUTO |
DO | SWP_CMD | 软化水泵启停命令 | Soft Water Pump Command | 关 | 开 | OFF | ON |
|
|
|
|
|
|
|
|
| ET | 膨胀水箱 | Expansion Tank |
|
|
|
|
| SM | 污水坑 | Sump |
|
|
|
|
| DWT | 生活水箱 | Domestic Water Tank |
|
|
|
|
| MT | 补水箱 | Makeup Tank |
|
|
|
|
| SWT | 软化水箱 | Soft Water Tank |
|
|
|
|
| PMP | 水泵 | Pump |
|
|
|
|
| SMP | 污水泵 | Sump Pump |
|
|
|
|
| DWP | 生活水泵 | Domestic Water Pump |
|
|
|
|
| MP | 补水泵 | Makeup Pump |
|
|
|
|
| SWP | 软化水泵 | Soft Water Pump |
|
|
|
|
| L | 液位 | Level |
|
|
|
|
| LS | 液位状态 | Level Status |
|
|
|
|
| LLL | 超低液位 | Low-low Level Status |
|
|
|
|
| LLL_ALM | 超低液位报警 | Low-low Level Alarm |
|
|
|
|
| LL | 低液位 | Low Level Status |
|
|
|
|
| HL | 高液位 | High Level Status |
|
|
|
|
| HHL | 超高液位 | High-high Level Status |
|
|
|
|
| HHL_ALM | 超高液位报警 | High-high Level Alarm |
|
|
|
|
| PSWP | 一次供水压力 | Primary Supply Water Pressure |
|
|
|
|
| PRWP | 一次回水压力 | Primary Return Water Pressure |
|
|
|
|
| PSWT | 一次供水温度 | Primary Supply Water Temperature |
|
|
|
|
| PRWT | 一次回水温度 | Primary Return Water Temperature |
|
|
|
|
| SSWP | 二次供水压力 | Secondary Supply Water Pressure |
|
|
|
|
| SRWP | 二次回水压力 | Secondary Return Water Pressure |
|
|
|
|
| SSWT | 二次供水温度 | Secondary Supply Water Temperature |
|
|
|
|
| SRWT | 二次回水温度 | Secondary Return Water Temperature |
|
|
|
|
| PVLV_CTL | 一次阀门控制 | Primary Valve Control |
|
|
|
|
| PCP | 一次循环泵 | Primary Circulating Water Pump | 关 | 开 | OFF | ON |
| SCP | 二次循环泵 | Secondary Circulating Water Pump | 关 | 开 | OFF | ON |
DI | PCP_STA | 一次侧循环泵运行状态 | Primary Circulating Pump Status | 关 | 开 | OFF | ON |
DI | PCP_FA | 一次侧循环泵故障报警 | Primary Circulating Pump Fault Alarm | 正常 | 报警 | OK | FLT |
DI | PCP_MA | 一次侧循环泵手自动状态 | Primary Circulating Pump Auto/Manual Select | 手动 | 自动 | MAN | AUTO |
DO | PCP_CMD | 一次侧循环泵启停命令 | Primary Circulating Pump Command | 关 | 开 | OFF | ON |
|
|
|
|
|
|
|
|
DI | SCP_STA | 二次侧循环泵运行状态 | Secondary Circulating Pump Status | 关 | 开 | OFF | ON |
DI | SCP_FA | 二次侧循环泵故障报警 | Secondary Circulating Pump Fault Alarm | 正常 | 报警 | OK | FLT |
DI | SCP_MA | 二次侧循环泵手自动状态 | Secondary Circulating Pump Auto/Manual Select | 手动 | 自动 | MAN | AUTO |
DO | SCP_CMD | 二次侧循环泵启停命令 | Secondary Circulating Pump Command | 关 | 开 | OFF | ON |