The control sequence can be set via P02.
The following sequences can be activated in the thermostat.
The available sequences depend on the application (selected via P01, see Control parameters).
|
Parameter | P02 = 0 | P02 = 1 | P02 = 2 | P02 = 3 | P02 = 4 |
Sequence | |||||
Available for basic application ⇓ | Heating only | Cooling only | H/C changeover auto via external water temperature sensor or remote switch | Manually select heating or cooling sequence (using HMI) | Heating and cooling sequence, 4-pipe |
2-pipe |
| ||||
|
2-pipe FCU for cooling + floor heating |
| ||||
4-pipe |
|
|
|
|
1) For manual changeover with 4-pipe applications, see 4-pipe fan coil unit.
- 4-pipe manual changeover (P02 = 3) means activating either cooling or heating outputs