• The AP Controller should be provided with power in the range of: 12V – 24V DC. The AP Power Supply must be protected by a fuse (2A).
  • An Audit Trail Message will be produced if the voltage level drops below 10.5V or goes above 26.5V.
  • Absolute maximum power ratings are: 9.5V – 29.5V DC.
  • The Reader Power Supply outputs are protected by a thermal fuse. In the event of a short-circuit the fuse will trip. The fuse will automatically reset in about 30 seconds if the fault has cleared.