Object type | Supported | Can be created dynamically | Can be deleted dynamically |
|---|---|---|---|
Analog Input | ☒ | ☐ | ☐ |
Analog Output | ☒ | ☐ | ☐ |
Analog Value | ☒ | ☐ | ☐ |
Averaging | ☐ | ☐ | ☐ |
Binary Input | ☒ | ☐ | ☐ |
Binary Output | ☒ | ☐ | ☐ |
Binary Value | ☒ | ☐ | ☐ |
Calendar | ☒ | ☒ | ☒ |
Command | ☒ | ☐ | ☐ |
Device | ☒ | ☐ | ☐ |
Event Enrollment | ☒ | ☒ | ☒ |
File | ☒ | ☐ | ☐ |
Group | ☐ | ☐ | ☐ |
Life-Safety-Point | ☐ | ☐ | ☐ |
Life-Safety-Zone | ☐ | ☐ | ☐ |
Loop | ☐ | ☐ | ☐ |
Multi-State Input | ☐ | ☐ | ☐ |
Multi-State Output | ☒ | ☐ | ☐ |
Multi-State Value | ☒ | ☐ | ☐ |
Notification Class | ☒ | ☒ | ☒ |
Program | ☒ | ☐ | ☐ |
Pulse-Converter | ☒ | ☐ | ☐ |
Schedule | ☒ | ☒ | ☒ |
Trend Log | ☒ | ☒ | ☒ |
Access Door | ☐ | ☐ | ☐ |
Event Log | ☒ | ☐ | ☐ |
Load Control | ☐ | ☐ | ☐ |
Structured-View | ☒ | ☐ | ☐ |
Trend Log Multiple | ☐ | ☐ | ☐ |
Access Point | ☐ | ☐ | ☐ |
Access Zone | ☐ | ☐ | ☐ |
Access User | ☐ | ☐ | ☐ |
Access Rights | ☐ | ☐ | ☐ |
Access Credential | ☐ | ☐ | ☐ |
Credential Data Input | ☐ | ☐ | ☐ |
Characterstring Value | ☐ | ☐ | ☐ |
Datetime Value | ☐ | ☐ | ☐ |
Large Analog Value | ☐ | ☐ | ☐ |
Bitstring Value | ☐ | ☐ | ☐ |
Octetstring Value | ☐ | ☐ | ☐ |
Time Value | ☐ | ☐ | ☐ |
Integer Value | ☐ | ☐ | ☐ |
Positive Integer Value | ☐ | ☐ | ☐ |
Date Value | ☐ | ☐ | ☐ |
Datetime Pattern Value | ☐ | ☐ | ☐ |
Time Pattern Value | ☐ | ☐ | ☐ |
Date Pattern Value | ☐ | ☐ | ☐ |
Network Security | ☐ | ☐ | ☐ |
Global Group | ☐ | ☐ | ☐ |
Notification Forwarder | ☐ | ☐ | ☐ |
Alert Enrollment | ☐ | ☐ | ☐ |
Channel | ☐ | ☐ | ☐ |
Lighting Output | ☐ | ☐ | ☐ |
Binary Lighting Output | ☐ | ☐ | ☐ |
Network Port | ☐ | ☐ | ☐ |
Timer | ☐ | ☐ | ☐ |
Elevator Group | ☐ | ☐ | ☐ |
Lift | ☐ | ☐ | ☐ |
Escalator | ☐ | ☐ | ☐ |
Accumulator | ☒ | ☐ | ☐ |
Analog Input
Properties | Supported | Readable (R)/Writable (W) | Range Restrictions |
|---|---|---|---|
Object_Identifier | ☒ | R |
|
Object_Name | ☒ | W |
|
Object_Type | ☒ | R |
|
Present_Value | ☒ | W |
|
Description | ☒ | W |
|
Device_Type | ☒ | W |
|
Status_Flags | ☒ | R |
|
Event_State | ☒ | R |
|
Reliability | ☒ | W |
|
Out_Of_Service | ☒ | W |
|
Event_Message_Texts | ☒ | R |
|
Units | ☒ | W |
|
Min_Pres_Value | ☒ | W |
|
Max_Pres_Value | ☒ | W |
|
Resolution | ☒ | W |
|
COV_Increment | ☒ | W |
|
Time_Delay | ☒ | W |
|
Notification_Class | ☒ | W |
|
High_Limit | ☒ | W |
|
Low_Limit | ☒ | W |
|
Deadband | ☒ | W |
|
Limit_Enable | ☒ | W |
|
Event_Enable | ☒ | W |
|
Acked_Transitions | ☒ | R |
|
Notify_Type | ☒ | W |
|
Event_Time_Stamps | ☒ | R |
|
Profile_Name | ☒ | R |
|
Event_Message_Texts_Config | ☒ | W |
|
Event_Detection_Enable | ☒ | R |
|
Event_Algorithm_Inhibit | ☒ | W |
|
Time_Delay_Normal | ☒ | W |
|
Reliability_Evaluation_Inhibit | ☒ | W |
|
Property_List | ☒ | R |
|
Analog Output
Properties | Supported | Readable (R)/Writable (W) | Range Restrictions |
|---|---|---|---|
Object_Identifier | ☒ | R |
|
Object_Name | ☒ | W |
|
Object_Type | ☒ | R |
|
Present_Value | ☒ | W |
|
Description | ☒ | W |
|
Device_Type | ☒ | W |
|
Status_Flags | ☒ | R |
|
Event_State | ☒ | R |
|
Reliability | ☒ | W |
|
Out_Of_Service | ☒ | W |
|
Units | ☒ | W |
|
Min_Pres_Value | ☒ | W |
|
Max_Pres_Value | ☒ | W |
|
Resolution | ☒ | W |
|
Priority_Array | ☒ | R |
|
Relinquish_Default | ☒ | W |
|
COV_Increment | ☒ | W |
|
Time_Delay | ☒ | W |
|
Notification_Class | ☒ | W |
|
High_Limit | ☒ | W |
|
Low_Limit | ☒ | W |
|
Deadband | ☒ | W |
|
Limit_Enable | ☒ | W |
|
Event_Enable | ☒ | W |
|
Acked_Transitions | ☒ | R |
|
Notify_Type | ☒ | W |
|
Event_Time_Stamps | ☒ | R |
|
Profile_Name | ☒ | R |
|
Event_Message_Texts | ☒ | R |
|
Event_Message_Texts_Config | ☒ | W |
|
Event_Detection_Enable | ☒ | R |
|
Event_Algorithm_Inhibit | ☒ | W |
|
Time_Delay_Normal | ☒ | W |
|
Reliability_Evaluation_Inhibit | ☐ | W |
|
Property_List | ☒ | R |
|
Analog Value
Properties | Supported | Readable (R)/Writable (W) | Range Restrictions |
|---|---|---|---|
Object_Identifier | ☒ | R |
|
Object_Name | ☒ | W |
|
Object_Type | ☒ | R |
|
Present_Value | ☒ | W |
|
Description | ☒ | W |
|
Status_Flags | ☒ | R |
|
Event_State | ☒ | R |
|
Reliability | ☒ | W |
|
Out_Of_Service | ☒ | W |
|
Units | ☒ | W |
|
Max_Pres_Value | ☒ | W |
|
Min_Pres_Value | ☒ | W |
|
COV_Increment | ☒ | W |
|
Time_Delay | ☒ | W |
|
Notification_Class | ☒ | W |
|
High_Limit | ☒ | W |
|
Low_Limit | ☒ | W |
|
Deadband | ☒ | W |
|
Limit_Enable | ☒ | W |
|
Event_Enable | ☒ | W |
|
Acked_Transitions | ☒ | R |
|
Notify_Type | ☒ | W |
|
Event_Time_Stamps | ☒ | R |
|
Profile_Name | ☒ | R |
|
Resolution | ☒ | W |
|
Event_Message_Texts | ☒ | R |
|
Event_Message_Texts_Config | ☒ | W |
|
Event_Detection_Enable | ☒ | R |
|
Event_Algorithm_Inhibit | ☒ | W |
|
Time_Delay_Normal | ☒ | W |
|
Reliability_Evaluation_Inhibit | ☐ | W |
|
Property_List | ☒ | R |
|
Priority_Array | ☒ | R |
|
Relinquish_Default | ☒ | W |
|
Binary Input
Properties | Supported | Readable (R)/Writable (W) | Range Restrictions |
|---|---|---|---|
Acked_Transitions | ☒ | R |
|
Active_Text | ☒ | W |
|
Alarm_Value | ☒ | W |
|
Notification_Class | ☒ | W |
|
Description | ☒ | W |
|
Device_Type | ☒ | W |
|
Elapsed_Active_Time | ☒ | W |
|
Event_Enable | ☒ | W |
|
Event_State | ☒ | R |
|
Inactive_Text | ☒ | W |
|
Notify_Type | ☒ | W |
|
Object_Identifier | ☒ | R |
|
Object_Name | ☒ | W |
|
Object_Type | ☒ | R |
|
Out_Of_Service | ☒ | W |
|
Polarity | ☒ | W |
|
Present_Value | ☒ | W |
|
Reliability | ☒ | W |
|
Status_Flags | ☒ | R |
|
Time_Delay | ☒ | W |
|
Time_Of_Active_Time_Reset | ☒ | R |
|
Event_Time_Stamps | ☒ | R |
|
Profile_Name | ☒ | R |
|
Event_Message_Texts | ☒ | R |
|
Event_Message_Texts_Config | ☒ | W |
|
Event_Detection_Enable | ☒ | R |
|
Event_Algorithm_Inhibit | ☒ | W |
|
Time_Delay_Normal | ☒ | W |
|
Reliability_Evaluation_Inhibit | ☐ | W |
|
Property_List | ☒ | R |
|
Change_Of_State_Count | ☒ | W |
|
Change_Of_State_Time | ☒ | R |
|
Time_Of_State_Count_Reset | ☒ | R |
|
Binary Output
Properties | Supported | Readable (R)/Writable (W) | Range Restrictions |
|---|---|---|---|
Object_Identifier | ☒ | R |
|
Object_Name | ☒ | W |
|
Object_Type | ☒ | R |
|
Present_Value | ☒ | W |
|
Description | ☒ | W |
|
Device_Type | ☒ | W |
|
Status_Flags | ☒ | R |
|
Event_State | ☒ | R |
|
Reliability | ☒ | W |
|
Out_Of_Service | ☒ | W |
|
Polarity | ☒ | W |
|
Inactive_Text | ☒ | W |
|
Active_Text | ☒ | W |
|
Event_Message_Texts | ☒ | R |
|
Event_Message_Texts_Config | ☒ | W |
|
Event_Detection_Enable | ☒ | R |
|
Elapsed_Active_Time | ☒ | W |
|
Time_Of_Active_Time_Reset | ☒ | R |
|
Minimum_Off_Time | ☒ | W |
|
Minimum_On_Time | ☒ | W |
|
Priority_Array | ☒ | R |
|
Relinquish_Default | ☒ | W |
|
Time_Delay | ☒ | W |
|
Notification_Class | ☒ | W |
|
Feedback_Value | ☒ | R |
|
Event_Enable | ☒ | W |
|
Acked_Transitions | ☒ | R |
|
Notify_Type | ☒ | W |
|
Event_Time_Stamps | ☒ | R |
|
Profile_Name | ☒ | R |
|
Event_Algorithm_Inhibit | ☒ | W |
|
Time_Delay_Normal | ☒ | W |
|
Reliability_Evaluation_Inhibit | ☐ | W |
|
Property_List | ☒ | R |
|
Change_Of_State_Count | ☒ | W |
|
Change_Of_State_Time | ☒ | R |
|
Time_Of_State_Count_Reset | ☒ | R |
|
Binary Value
Properties | Supported | Readable (R)/Writable (W) | Range Restrictions |
|---|---|---|---|
Object_Identifier | ☒ | R |
|
Object_Name | ☒ | W |
|
Object_Type | ☒ | R |
|
Present_Value | ☒ | W |
|
Description | ☒ | W |
|
Status_Flags | ☒ | R |
|
Event_State | ☒ | R |
|
Reliability | ☒ | W |
|
Out_Of_Service | ☒ | W |
|
Inactive_Text | ☒ | W |
|
Active_Text | ☒ | W |
|
Event_Message_Texts | ☒ | R |
|
Event_Message_Texts_Config | ☒ | W |
|
Event_Detection_Enable | ☒ | R |
|
Elapsed_Active_Time | ☒ | W |
|
Time_Of_Active_Time_Reset | ☒ | R |
|
Minimum_Off_Time | ☒ | W |
|
Minimum_On_Time | ☒ | W |
|
Priority_Array | ☒ | R |
|
Relinquish_Default | ☒ | W |
|
Time_Delay | ☒ | W |
|
Notification_Class | ☒ | W |
|
Alarm_Value | ☒ | W |
|
Event_Enable | ☒ | W |
|
Acked_Transitions | ☒ | R |
|
Notify_Type | ☒ | W |
|
Event_Time_Stamps | ☒ | R |
|
Profile_Name | ☒ | R |
|
Event_Algorithm_Inhibit | ☒ | W |
|
Time_Delay_Normal | ☒ | W |
|
Reliability_Evaluation_Inhibit | ☐ | W |
|
Property_List | ☒ | R |
|
Change_Of_State_Count | ☒ | W |
|
Change_Of_State_Time | ☒ | R |
|
Time_Of_State_Count_Reset | ☒ | R |
|
Calendar
Properties | Supported | Readable (R)/Writable (W) | Range Restrictions |
|---|---|---|---|
Object_Identifier | ☒ | R |
|
Object_Name | ☒ | W |
|
Object_Type | ☒ | R |
|
Description | ☒ | W |
|
Present_Value | ☒ | R |
|
Date_List | ☒ | W |
|
Profile_Name | ☒ | R |
|
Property_List | ☒ | R |
|
Command
Properties | Supported | Readable (R)/Writable (W) | Range Restrictions |
|---|---|---|---|
Object_Identifier | ☒ | R |
|
Object_Name | ☒ | W |
|
Object_Type | ☒ | R |
|
Description | ☒ | W |
|
Action | ☒ | W |
|
Action-Text | ☒ | W |
|
All-Writes-Successful | ☒ | R |
|
In-Process | ☒ | R |
|
Profile_Name | ☒ | R |
|
Property_List | ☒ | R |
|
Device
Properties | Supported | Readable (R)/Writable (W) | Range Restrictions |
|---|---|---|---|
Object_Identifier | ☒ | R |
|
Object_Name | ☒ | R |
|
Object_Type | ☒ | R |
|
System_Status | ☒ | R |
|
Vendor_Name | ☒ | R |
|
Vendor_Identifier | ☒ | R |
|
Model_Name | ☒ | R |
|
Firmware_Revision | ☒ | R |
|
Application_Software_Version | ☒ | R |
|
Location | ☒ | W |
|
Description | ☒ | W |
|
Protocol_Version | ☒ | R |
|
Protocol_Revision | ☒ | R |
|
Protocol_Services_Supported | ☒ | R |
|
Protocol_Object_Types_Supported | ☒ | R |
|
Object_List | ☒ | R |
|
Structured_Object_List | ☒ | R |
|
Max_APDU_Length_Accepted | ☒ | R |
|
Segmentation_Supported | ☒ | R |
|
Max_Segments_Accepted | ☒ | R |
|
VT_Classes_Supported | ☐ |
|
|
Active_VT_Sessions | ☐ |
|
|
Local_Time | ☒ | W |
|
Local_Date | ☒ | W |
|
UTC_Offset | ☒ | R |
|
Daylight_Savings_Status | ☒ | R |
|
APDU_Segment_Timeout | ☒ | R |
|
APDU_Timeout | ☒ | W |
|
Number_Of_APDU_Retries | ☒ | W |
|
Property_List | ☒ | R |
|
Time_Synchronization_Recipients | ☒ | W |
|
Max_Master | ☒ | R1) |
|
Max_Info_Frames | ☒ | R1) |
|
Device_Address_Binding | ☒ | R |
|
Database_Revision | ☒ | R |
|
Configuration_Files | ☒ | R |
|
Last_Restore_Time | ☒ | R |
|
Backup_Failure_Timeout | ☒ | W |
|
Backup_Preparation_Time | ☒ | R |
|
Restore_Preparation_Time | ☒ | R |
|
Restore_Completion_Time | ☒ | R |
|
Backup_And_Restore_State | ☒ | R |
|
Active_COV_Subscriptions | ☒ | R |
|
Slave_Proxy_Enable | ☐ |
|
|
Manual_Slave_Adress_Binding | ☐ |
|
|
Auto_Slave_Discovery | ☐ |
|
|
Slave_Address_Binding | ☐ |
|
|
Last_Restart_Reason | ☒ | R |
|
Time_Of_Device_Restart | ☒ | R |
|
Restart_Notification_Recipients | ☒ | W |
|
UTC_Time_Synchronization_Recipients | ☒ | W |
|
Time_Synchronization_Interval | ☒ | W |
|
Align_Intervals | ☒ | W |
|
Interval_Offset | ☒ | W |
|
Profile_Name | ☒ | R |
|
1) Supported by PXC7.E400.A
File
Properties | Supported | Readable (R)/Writable (W) | Range Restrictions |
|---|---|---|---|
Object_Identifier | ☒ | R |
|
Object_Name | ☒ | W |
|
Object_Type | ☒ | R |
|
Description | ☒ | W |
|
File_Type | ☒ | R |
|
File_Size | ☒ | W |
|
Modification_Date | ☒ | R |
|
Archive | ☒ | R |
|
Read_Only | ☒ | R |
|
File_Access_Method | ☒ | R |
|
Property_List | ☒ | R |
|
Profile_Name | ☒ | R |
|
Multi-state Input
Properties | Supported | Readable (R)/Writable (W) | Range Restrictions |
|---|---|---|---|
Object_Identifier | ☒ | R |
|
Object_Name | ☒ | W |
|
Object_Type | ☒ | R |
|
Present_Value | ☒ | W |
|
Description | ☒ | W |
|
Device_Type | ☒ | W |
|
Status_Flags | ☒ | R |
|
Event_State | ☒ | R |
|
Reliability | ☒ | W |
|
Out_Of_Service | ☒ | W |
|
Number_Of_States | ☒ | R |
|
State_Text | ☒ | W |
|
Time_Delay | ☒ | W |
|
Notification_Class | ☒ | W |
|
Alarm_Values | ☒ | W |
|
Fault_Values | ☒ | W |
|
Event_Enable | ☒ | W |
|
Acked_Transitions | ☒ | R |
|
Notify_Type | ☒ | W |
|
Event_Time_Stamps | ☒ | R |
|
Profile_Name | ☒ | R |
|
Event_Message_Texts | ☒ | R |
|
Event_Message_Texts_Config | ☒ | W |
|
Event_Detection_Enable | ☒ | R |
|
Event_Algorithm_Inhibit | ☒ | W |
|
Time_Delay_Normal | ☒ | W |
|
Reliability_Evaluation_Inhibit | ☐ | W |
|
Property_List | ☒ | R |
|
Multi-state Output
Properties | Supported | Readable (R)/Writable (W) | Range Restrictions |
|---|---|---|---|
Object_Identifier | ☒ | R |
|
Object_Name | ☒ | W |
|
Object_Type | ☒ | R |
|
Present_Value | ☒ | W |
|
Description | ☒ | W |
|
Device_Type | ☒ | W |
|
Status_Flags | ☒ | R |
|
Event_State | ☒ | R |
|
Reliability | ☒ | W |
|
Out_Of_Service | ☒ | W |
|
Number_Of_States | ☒ | R |
|
State_Text | ☒ | W |
|
Priority_Array | ☒ | R |
|
Relinquish_Default | ☒ | W |
|
Time_Delay | ☒ | W |
|
Notification_Class | ☒ | W |
|
Feedback_Value | ☒ | R |
|
Event_Enable | ☒ | W |
|
Acked_Transitions | ☒ | R |
|
Notify_Type | ☒ | W |
|
Event_Time_Stamps | ☒ | R |
|
Profile_Name | ☒ | R |
|
Event_Message_Texts | ☒ | R |
|
Event_Message_Texts_Config | ☒ | W |
|
Event_Detection_Enable | ☒ | R |
|
Event_Algorithm_Inhibit | ☒ | W |
|
Time_Delay_Normal | ☒ | W |
|
Reliability_Evaluation_Inhibit | ☐ | W |
|
Property_List | ☒ | R |
|
Multi-state Value
Properties | Supported | Readable (R)/Writable (W) | Range Restrictions |
|---|---|---|---|
Object_Identifier | ☒ | R |
|
Object_Name | ☒ | W |
|
Object_Type | ☒ | R |
|
Present_Value | ☒ | W |
|
Description | ☒ | W |
|
Status_Flags | ☒ | R |
|
Event_State | ☒ | R |
|
Reliability | ☒ | W |
|
Out_Of_Service | ☒ | W |
|
Number_Of_States | ☒ | R |
|
State_Text | ☒ | W |
|
Priority_Array | ☒ | R |
|
Relinquish_Default | ☒ | W |
|
Time_Delay | ☒ | W |
|
Notification_Class | ☒ | W |
|
Alarm_Values | ☒ | W |
|
Event_Enable | ☒ | W |
|
Acked_Transitions | ☒ | R |
|
Notify_Type | ☒ | W |
|
Event_Time_Stamps | ☒ | R |
|
Profile_Name | ☒ | R |
|
Event_Message_Texts | ☒ | R |
|
Event_Message_Texts_Config | ☒ | W |
|
Event_Detection_Enable | ☒ | R |
|
Event_Algorithm_Inhibit | ☒ | W |
|
Time_Delay_Normal | ☒ | W |
|
Reliability_Evaluation_Inhibit | ☐ | W |
|
Property_List | ☒ | R |
|
Notification Class
Properties | Supported | Readable (R)/Writable (W) | Range Restrictions |
|---|---|---|---|
Object_Identifier | ☒ | R |
|
Object_Name | ☒ | W |
|
Object_Type | ☒ | R |
|
Description | ☒ | W |
|
Notification_Class | ☒ | R |
|
Priority | ☒ | W |
|
Ack_Required | ☒ | W |
|
Recipient_List | ☒ | W |
|
Profile_Name | ☒ | R |
|
Property_List | ☒ | R |
|
Schedule
Properties | Supported | Readable (R)/Writable (W) | Range Restrictions |
|---|---|---|---|
Object_Identifier | ☒ | R |
|
Object_Name | ☒ | W |
|
Object_Type | ☒ | R |
|
Present_Value | ☒ | W |
|
Description | ☒ | W |
|
Effective_Period | ☒ | W |
|
Weekly_Schedule | ☒ | W |
|
Exception_Schedule | ☒ | W |
|
Schedule_Default | ☒ | W |
|
List_Of_Object_Property_References | ☒ | W |
|
Priority_For_Writing | ☒ | W |
|
Status_Flags | ☒ | R |
|
Reliability | ☒ | W |
|
Out_Of_Service | ☒ | W |
|
Profile_Name | ☒ | R |
|
Reliability_Evaluation_Inhibit | ☐ | W |
|
Property_List | ☒ | R |
|
Program
Properties | Supported | Readable (R)/Writable (W) | Range Restrictions |
|---|---|---|---|
Object_Identifier | ☒ | R |
|
Object_Name | ☒ | R |
|
Object_Type | ☒ | R |
|
Program_State | ☒ | R |
|
Program_Change | ☒ | W |
|
Reason_For_Halt | ☐ | R |
|
Description_Of_Halt | ☐ | R |
|
Reliability_Evaluation_Inhibit | ☐ | W |
|
Description | ☒ | W |
|
Property_List | ☒ | R |
|
Status_Flags | ☒ | R |
|
Reliability | ☒ | R |
|
Out_Of_Service | ☒ | R |
|
Profile_Name | ☒ | R |
|
Pulse Converter
Properties | Supported | Readable (R)/Writable (W) | Range Restrictions |
|---|---|---|---|
Object_Identifier | ☒ | R |
|
Object_Name | ☒ | W |
|
Object_Type | ☒ | R |
|
Present_Value | ☒ | W |
|
Description | ☒ | W |
|
Event_Enable | ☒ | W |
|
Status_Flags | ☒ | R |
|
Event_State | ☒ | R |
|
Reliability | ☒ | W |
|
Out_Of_Service | ☒ | W |
|
Scale_Factor | ☒ | W |
|
Units | ☒ | W |
|
COV_Period | ☒ | R |
|
COV_Increment | ☒ | W |
|
Value_Change_Time | ☒ | R |
|
Value_Before_Change | ☒ | R |
|
Value_Set | ☒ | W |
|
Profile_Name | ☒ | R |
|
Property_List | ☒ | R |
|
Reliability_Evaluation_Inhibit | ☐ | W |
|
Time_Delay | ☒ | W |
|
Notification_Class | ☒ | W |
|
High_Limit | ☒ | W |
|
Low_Limit | ☒ | W |
|
Deadband | ☒ | W |
|
Limit_Enable | ☒ | W |
|
Acked_Transitions | ☒ | R |
|
Notify_Type | ☒ | W |
|
Event_Time_Stamps | ☒ | R |
|
Event_Message_Texts | ☒ | R |
|
Event_Message_Texts_Config | ☒ | W |
|
Event_Detection_Enable | ☒ | R |
|
Event_Algorithm_Inhibit | ☒ | W |
|
Time_Delay_Normal | ☒ | W |
|
Adjust_Value | ☒ | W |
|
Count | ☒ | R |
|
Count_Before_Change | ☒ | R |
|
Count_Change_Time | ☒ | R |
|
Update_Time | ☒ | R |
|
Trend Log
Properties | Supported | Readable (R)/Writable (W) | Range Restrictions |
|---|---|---|---|
Object_Identifier | ☒ | R |
|
Object_Name | ☒ | W |
|
Object_Type | ☒ | R |
|
Description | ☒ | W |
|
Enable | ☒ | W |
|
Start_Time | ☒ | W |
|
Stop_Time | ☒ | W |
|
Log_DeviceObjectProperty | ☒ | R |
|
Log_Interval | ☒ | W |
|
COV_Resubscription_Interval | ☒ | R |
|
Event_Detection_Enable | ☒ | R |
|
Stop_When_Full | ☒ | W |
|
Buffer_Size | ☒ | W |
|
Log_Buffer | ☒ | R |
|
Record_Count | ☒ | W |
|
Total_Record_Count | ☒ | R |
|
Notification_Threshold | ☒ | W |
|
Records_Since_Notification | ☒ | R |
|
Last_Notify_Record | ☒ | R |
|
Event_State | ☒ | R |
|
Notification_Class | ☒ | W |
|
Event_Enable | ☒ | W |
|
Acked_Transitions | ☒ | R |
|
Notify_Type | ☒ | R |
|
Event_Time_Stamps | ☒ | R |
|
Profile_Name | ☒ | R |
|
Logging_Type | ☒ | W |
|
Align_Intervals | ☒ | W |
|
Interval_Offset | ☒ | W |
|
Reliability_Evaluation_Inhibit | ☐ | W |
|
Status_Flags | ☒ | R |
|
Reliability | ☒ | R |
|
Property_List | ☒ | R |
|
Accumulator
Properties | Supported | Readable (R)/Writable (W) | Range Restrictions |
|---|---|---|---|
Object_Identifier | ☒ | R |
|
Object_Name | ☒ | W |
|
Object_Type | ☒ | R |
|
Present_Value | ☒ | W |
|
Description | ☒ | W |
|
Device_Type | ☒ | R |
|
Status_Flags | ☒ | R |
|
Event_State | ☒ | R |
|
Reliability | ☒ | W |
|
Out_Of_Service | ☒ | W |
|
Scale | ☒ | W |
|
Units | ☒ | W |
|
Prescale | ☒ | W |
|
Max_Pres_Value | ☒ | R |
|
Value_Change_Time | ☒ | R |
|
Value_Before_Change | ☒ | R |
|
Value_Set | ☒ | W |
|
Profile_Name | ☒ | R |
|
Property_List | ☒ | R |
|
Reliability_Evaluation_Inhibit | ☐ | W |
|
Event Log
Properties | Supported | Readable (R)/Writable (W) | Range Restrictions |
|---|---|---|---|
Object_Identifier | ☒ | R |
|
Object_Name | ☒ | W |
|
Object_Type | ☒ | R |
|
Description | ☒ | W |
|
Status_Flags | ☒ | R |
|
Event_State | ☒ | R |
|
Reliability | ☒ | R |
|
Enable | ☒ | W |
|
Start_Time | ☒ | W |
|
Stop_Time | ☒ | W |
|
Stop_When_Full | ☒ | W |
|
Buffer_Size | ☒ | W |
|
Log_Buffer | ☒ | R |
|
Record_Count | ☒ | W |
|
Total_Record_Count | ☒ | R |
|
Notification_Threshold | ☒ | W |
|
Records_Since_Notification | ☒ | R |
|
Last_Notify_Record | ☒ | R |
|
Notification_Class | ☒ | W |
|
Event_Enable | ☒ | W |
|
Acked_Transitions | ☒ | R |
|
Notify_Type | ☒ | R |
|
Event_Time_Stamps | ☒ | R |
|
Profile_Name | ☒ | R |
|
Event_Detection_Enable | ☒ | R |
|
Reliability_Evaluation_Inhibit | ☐ | W |
|
Property_List | ☒ | R |
|
Structured View
Properties | Supported | Readable (R)/Writable (W) | Range Restrictions |
|---|---|---|---|
Object_Identifier | ☒ | R |
|
Object_Name | ☒ | W |
|
Object_Type | ☒ | R |
|
Description | ☒ | W |
|
Node_Type | ☒ | R |
|
Node_Subtype | ☒ | R |
|
Subordinate_List | ☒ | R |
|
Subordinate_Annotations | ☒ | R |
|
Profile_Name | ☒ | R |
|
Property_List | ☒ | R |
|
Event Enrollment
Properties | Supported | Readable (R)/Writable (W) | Range Restrictions |
|---|---|---|---|
Acked_Transitions | ☒ | R |
|
Notification_Class | ☒ | W |
|
Description | ☒ | W |
|
Event_Enable | ☒ | W |
|
Event_State | ☒ | R |
|
Notify_Type | ☒ | W |
|
Object_Identifier | ☒ | R |
|
Object_Name | ☒ | W |
|
Object_Type | ☒ | R |
|
Profile_Name | ☒ | R |
|
Event_Message_Texts | ☒ | R |
|
Event_Message_Texts_Config | ☒ | W |
|
Event_Detection_Enable | ☒ | W |
|
Event_Algorithm_Inhibit | ☒ | W |
|
Property_List | ☒ | R |
|
Event_Type | ☒ | R |
|
Object_Property_Reference | ☒ | R |
|
Event_Parameters | ☒ | R |
|
Reliability | ☒ | R |
|
Status_Flags | ☒ | R |
|
Time_Delay_Normal | ☒ | W |
|
Event_Time_Stamps | ☒ | R |
|