The Modbus Connector allows to import a device and datapoint configuration in bulk via csv template file. Export of the configuration is also possible.

  • You are in the Modbus Connector user interface.
  1. Go to Configuration.
  1. Select Template.
  1. Open modbus_template.csv file and modify the device and datapoint configuration. Maximum number of datapoints for Modbus configuration is 250.
  1. Select Stop connector.

Import of the configuration file overwrites all present configuration of the Modbus connector.

  1. Select Import and attach the modified modbus_template.csv file.
  1. Select Yes.

If there is an error in the configuration file, an error message displays and the import aborts.

  • Configuration is imported in the Modbus connector.

Exporting Modbus configuration

  • You are in the Modbus Connector user interface.
  1. Go to Configuration.
  1. Select Export.
  • Configuration file is saved in your local download folder.