General

General aspects

TXS power supply modules for TXM modules

For calculation of the necessary TXS power supply modules, see TXM I/O modules

Panel layout

Devices

Dimensions L x W x H

PXC4-2...

PXC5.E003

PXC5.E24

PXC7...

124 x 198 x 70 mm

124 x 144 x 70 mm

124 x 270 x 70 mm

124 x 198 x 70 mm

TXM1... I/O modules

64 x 98 x 70 mm

TXS1.12... power supply module

TXS1.EF bus connection module

96 x 98 x 70 mm

32 x 98 x 70 mm

TXA1.IBE Island bus expansion module

32 x 98 x 70 mm

Limitation in the number of TXM modules

The PXC4-2, PXC5.E24, and PXC7 automation stations support two communication modes for the TXM modules:

Polling mode (default mode)

Support of up to 64 TXM modules per automation station

Event mode

Support of up to 8 TXM modules per automation station

Installation details

For installation details, see:

CM2N8183

Power supply module

TXS1.12F10

CM2N8183

Bus connection module

TXS1.EF10

CM2N8184

Island bus expansion module

TXA1.IBE

CM110562

TX-I/O engineering and installation manual

Small plants powered by automation station (PXC4-2, PXC5.E24, and PXC7 supply up to 300 mA)

 

1 PXC7...

 

Automation station

2 TXM...

I/O modules

Example:
2 x TXM1.8U, 1 x TXM1.6R, 1 x TXM1.4D3R, 1 x TXM1.16D

 

1 PXC5.E24

 

Automation station

2 TXM...

I/O modules

Example:
1 x TXM1.8U, 1 x TXM1.6R, 1 x TXM1.6D

 

1 PXC4-2...

 

Automation station

2 TXM...

I/O modules

Example:
1 x TXM1.4D3R

Medium to large plants

 

1 PXC...

 

Automation station

2 TXS1.12F10

Power supply module

3 TXS1.EF10

Bus connection module
(if no TXS12.EF in this rail)

4 TXM...

I/O modules

Example:
TXM1.8U, TXM1.6R

- - - -

-------

Island Bus

24 VAC (24 VDC)

All TXM modules need an address key TXA1.Kxx with a unique number.

Decentralized TXM Island

 

1 PXC...

 

Automation station

2 TXS1.12F10

Power supply module

3 TXS1.EF10

Bus connection module

4 TXM...

I/O modules

5 TXA1.IBE

Island bus expansion module

--- - --- -

Decentralized I/O Island: connection via Island bus expansion modules

Total distance of decentralized I/O Island:
2 x 200 m cable lengths from PXC5.E24 or PXC7 automation station

Total number of decentralized I/O Islands per PXC5.E24 or PXC7 automation station: 8

Use module series C and higher.

All TXM modules need an address key TXA1.Kxx with a unique number for each PXC7 automation station.