The wireless room sensor, QPA2892/WI indicates the current CO2 level via its CO2 traffic light mode.

With activated CO2 traffic light mode, the indoor air quality level is indicated by a multicolor indication on the device. The CO2 traffic light mode has three states:

  • Green: Good room air quality (CO2 level below CO2 Thresholds1).
  • Yellow: Fair room air quality (CO2 level between CO2 Thresholds1 and CO2 Thresholds2).
  • Red: Poor room air quality (CO2 level above CO2 Thresholds2).

 

To activate this functionality, the CO2 traffic light mode must be activated.

  • Access Device parameters of the device (see Device parameters)
  • Go to parameter CO2 LED Mode
  • Select the LED response for traffic light indication (default: "0 Good: Green off; Okay: Yellow off; Poor: Red off")
  • Optional: Adjust the CO2 Thresholds
  • Save the settings with Apply
  • The CO2 traffic light indicator is on for 6 s while CO2 LED Mode is adjusted.