To communicate with northbound controllers and a building automation and control system from Siemens or third-party suppliers via BACnet/IP over Ethernet systems, the KNX IoT to BACnet/IP gateway (OCT200.KNBA) is able to receive/send data from/to IoT devices via wireless connection (KNX IoT over Thread) and translate this data to BACnet references. The controllers and systems from Siemens include:

  • PXC4/5/7
  • DXR2 and PXC3
  • X200 and X300
  • Building X
  • Desigo CC
  • Desigo Optic
  • Desigo Classic
  • Desigo Control Point

Max. 100 Thread devices can be connected to one KNX IoT to BACnet/IP gateway. If more than 100 devices must be connected, multiple KNX IoT to BACnet/IP gateways must be used.

  • Max. 32 end devices and 22 Thread mesh extenders can be connected directly to one KNX IoT to BACnet/IP gateway.
  • Max. 22 end devices can be connected directly to one Thread mesh extender.

 

Topology

Key

BACS

Building automation and control system

BMS

Building management system