When you select an event, you can check its details and properties of the event source in the event-related applications on the right.

Event Details

Information about the event currently being processed is displayed in the Event Details tab.

 

1

What occurred in the system. Namely, event category color, event cause description, intervention text (subsystem-dependent), source state, and event state.

State icon

Source State

Event State

Description

Active

Unprocessed

Event condition is active and not cleared.

The event has not been acknowledged.

The condition which caused the alarm still exists.

Active

Waiting for Condition

Event condition is active and not cleared.

The event has been acknowledged.

The condition which caused the alarm still exists.

Quiet

Unprocessed

Event condition is not active and not cleared.

The event has been acknowledged.

Quiet

Ready to be Reset

The source state is back to normal condition.

Event condition is no longer active and now can be cleared.

2

Where the event occurred in the system.
Namely, icon and name of the event-source object, event-source object and location.

You can also inspect the event source, and check event source information.
For instructions, see Get More Information About the Event Source.

3

When the event occurred.

4

Event handling commands.
For instructions, see Send Event Handling Commands.

5

Open the More expander to view additional information about the selected event.
For instructions, see Get More Information About the Event Source.

6

Open the Event Notes expander to handle event notes.
For instructions, see Handle Event Notes.

7

Switches to investigate the system.
For instructions, see Handling an Event with Investigative Treatment.

Properties of the Object in Alarm