• If you have non-application P1 devices that are not contained in the CT database, these devices can be discovered using CT Database Update Tool (CTDUT).
    NOTE: These devices must be defined in the CT database for accurate estimation and complete migration to PXC7.A. See the CT Database Update Tool in CT for more information.
  • In order to upgrade MBC/MEC to the PXC7.A, the existing Fast Forward Tool will be used to migrate to a PXC Modular. This pre-work is required (using CT FF) to complete prior to converting the final step in DT+.
  • Migrating to the PXC Modular provides the “container” to convert the MBC/MEC data (slope/intercepts, sensor types, etc.). The actual PXC modular hardware configuration in the FF tool is not relevant to the final PXC7.A migration.
  • The TX-I/O will be reused, ensure the configuration/selections are appropriate for the final migration to the PXC7.A.
  • Familiarize yourself with the TX-I/O Island Bus by reviewing the following documentation:
    • TX-I/O Island Bus Installation Instructions (553-142)
    • TX-I/O Island Bus Start-up Procedures (145-604)
    • TX-I/O Island Bus Technical Reference Manual (145-981)
    • APOGEE Wiring Guidelines for Field Panels and Equipment Controllers (125-3002)
  • For technical or ordering information, see the following documentation for Migration products:
    • Fast Forward Migration Getting Started Manual (545-328)
    • Fast Forward Migration Configuration and Sizing Guidelines (145-950), which provides ordering information for the Migration kits.
    • Fast Forward Migration Technical Reference (145-951), which provides a detailed description and specifications for the Migration kits.
  • Fast Forward Estimator Instruction Manual (145-500-3P2-INST)