These properties are only available when Subsystem is set to P1 BIM POS.

BACnet Property

Short name

BACnet Description

Notes

Allowed-Signal-Types

SigTypSprtd

Supported signal types

A read-only proprietary property that specifies a selectable set of physical actuated output types. Supported signals:
I420, U10

Signal-Type

Signal-Type

SigTyp

A writable proprietary enumerated property that specifies the physical actuated output type selected for the Analog-Output object instance. The enumeration range corresponds to the Allowed-Signal-Types.

Present-Value-1

PrcVal1

Process value 1

A writable proprietary property that specifies the scaled output value, in engineering units, that corresponds to the physical output value, Signal-Value-1.

Signal-Value-1

SigVal1

Signal value 1

A writable proprietary property that specifies a raw unscaled physical output value used to define the two-point sensed value conversion equation. A two-point method is used rather than the slope-intercept method.

Present-Value-2

PrcVal2

Process value 2

A writable proprietary property that specifies the scaled output value, in engineering units, that corresponds to the physical output value, Signal-Value-2.

Signal-Value-2

PrcVal2

Signal value 2

A writable proprietary property that specifies a second raw unscaled physical output value used to define the two-point sensed value conversion equation. A two-point method is used rather than the slope-intercept method.

COV-Repetition-Timer

TiExcgRptCl

COV repetition time

A writable proprietary enumerated property that configures the time interval between value updates from the Output object to data acquisition. Data acquisition will be updated even if the Output value does not change.