These properties are only available when Subsystem is set to PXM POS.
BACnet Property | Short name | BACnet Description | Notes |
---|---|---|---|
Allowed-Signal-Types | SigTypSprtd | Supported signal types | A read-only proprietary property that specifies a selectable set of physical actuated output types. Supported signals: |
Signal-Type | Signal-Type | SigTyp | A writable proprietary enumerated property that specifies the physical actuated output type selected for the Analog-Output object instance. The enumeration range corresponds to the Allowed-Signal-Types. |
Present-Value-1 | PrcVal1 | Process value 1 | A writable proprietary property that specifies the scaled output value, in engineering units, that corresponds to the physical output value, Signal-Value-1. |
Signal-Value-1 | SigVal1 | Signal value 1 | A writable proprietary property that specifies a raw unscaled physical output value used to define the two-point sensed value conversion equation. A two-point method is used rather than the slope-intercept method. |
Present-Value-2 | PrcVal2 | Process value 2 | A writable proprietary property that specifies the scaled output value, in engineering units, that corresponds to the physical output value, Signal-Value-2. |
Signal-Value-2 | SigVal2 | Signal value 2 | A writable proprietary property that specifies a second raw unscaled physical output value used to define the two-point sensed value conversion equation. A two-point method is used rather than the slope-intercept method. |
COV-Repetition-Timer | TiExcgRptCl | COV repetition time | A writable proprietary enumerated property that configures the time interval between value updates from the Output object to data acquisition. Data acquisition will be updated even if the Output value does not change. |