These properties are only available when Subsystem is set to P1 TEC POS.

BACnet Property

Short name

BACnet Description

Notes

Present-Value-1

PrcVal1

Process value 1

A writable proprietary property that specifies the scaled output value, in engineering units, that corresponds to the physical output value, Signal-Value-1.

Signal-Value-1

SigVal1

Signal value 1

A writable proprietary property that specifies a raw unscaled physical output value used to define the two-point sensed value conversion equation. A two-point method is used rather than the slope-intercept method.

Present-Value-2

PrcVal2

Process value 2

A writable proprietary property that specifies the scaled output value, in engineering units, that corresponds to the physical output value, Signal-Value-2.

Signal-Value-2

PrcVal2

Signal value 2

A writable proprietary property that specifies a second raw unscaled physical output value used to define the two-point sensed value conversion equation. A two-point method is used rather than the slope-intercept method.