These properties are only available when Subsystem is set to P1 TEC MEASURE.

BACnet Property

Short name

BACnet Description

Notes

Present-Value-1

PrcVal1

Process value 1

Defines the first physical value in engineering units of the conversion characteristic to calculate the present value out of the measured sensor value.

Signal-Value-1

SigVal1

Signal value 1

Defines the first signal value of the conversion characteristic to calculate the present value out of the measured sensor value.

Present-Value-2

PrcVal2

Process value 2

Defines the second physical value in engineering units of the conversion characteristic to calculate the present value out of the measured sensor value.

Signal-Value-2

SigVal2

Signal value 2

Defines the second signal value of the conversion characteristic to calculate the present value out of the measured sensor value.