These properties are only available when Subsystem is set to P1 BIM MEASURE.
BACnet Property | Short name | BACnet Description | Notes |
---|---|---|---|
Allowed-Signal-Types | SigTypSprtd | Supported signal types | A read-only proprietary property that specifies a selectable set of sensor types for the input. Input/sensor types are provided for temperature, resistance, current, and voltage. Supported signal types: I420, U10, NI1K, PT1K375, PT1K385, NTC10K, NTC100K |
Signal-Type | Signal-Type | SigTyp | The subset of supported signal types is HW specific and depends on the Allowed-Signal-Types property. |
Present-Value-1 | PrcVal1 | Process value 1 | Defines the first physical value in engineering units of the conversion characteristic to calculate the present value out of the measured sensor value. |
Signal-Value-1 | SigVal1 | Signal value 1 | Defines the first signal value of the conversion characteristic to calculate the present value out of the measured sensor value. |
Present-Value-2 | PrcVal2 | Process value 2 | Defines the second physical value in engineering units of the conversion characteristic to calculate the present value out of the measured sensor value. |
Signal-Value-2 | PrcVal2 | Signal value 2 | Defines the second signal value of the conversion characteristic to calculate the present value out of the measured sensor value. |
COV-Signal-Limit | RawValCOV | COV increment signal value | Throttle |
COV-Repetition-Timer | TiExcgRptCl | COV repetition time | Heartbeat |