This document covers migrating from a P2 MBC/MEC to a BACnet PXC7.A (IP only) automation station.

Migration Note:

Not all devices are supported by the PXC7.A, these devices (DPU/MPU/SCU/UC) need to be migrated to supported devices in order for the PXC7.A to recognize them.

PXC7.A does not support RS-485 ALN. If the MBC/MEC is on an RS-485 P2 ALN, plan to run Ethernet and add to job estimates.

For detailed information on migrating legacy panels (i.e., from an MBC/MEC to PXCM) see the existing migration processes.