BACnet Property

Short name

Desigo Attribute

Notes

object-identifier

ObjId

Object identifier

BV: 3002010

object-name

ObjNam

Object name

device-object-name:Holiday
The object-name of the local Device Object + ':' + "Holiday". For example, MyDevice:Holiday.

present-value

PrVal

Present value

A standard BACnet property that indicates whether the current day is a holiday. The present-value property will be active if the current day appears in a PPCL Holiday() statement in the local device, otherwise inactive.

NOTE: The Holiday() PPCL statement and the Holiday object are provided for backward compatibility with existing programs and should not be used on new projects.

inactive-text

IactvTxt

Inactive text

Default value: "normal".

active-text

ActvTxt

Active text

Default value: "holiday".