BACnet Property

Short name

Desigo Attribute

Notes

Selected-Peripheral-Device-Type

SelPrphDev

Selected field device type

A writable (local only) proprietary enumerated property, Selected-Peripheral-Device-Type, that specifies the P1 device type.

Local-Point-Selector

LocalPntSel

Selective unbundle

A writable property that specifies which P1 points are available as BACnet objects.

Download-Initial-Values

LdInitVals

Load initial values

A writable property that specifies if initial values are downloaded after a TEC returns from failure.

P1-Device-Units

P1DevUnits

P1 device units

A read-only proprietary enumerated property that specifies the unit system for the P1 device.
Enumeration: international-system, US-System

NOTE: The system of units is set in the device object.

P1-Night-Override

P1NightOvrd

P1 night override

A writable proprietary property that specifies the amount of time (in hours) that a TEC's DAY.NGT point will be overridden when the connected room temperature sensor's override switch is pressed.

P1-Instance-Base

P1InstBase

P1 instance base

A read-only proprietary property that defines the instance number of the first object for the P1 device that is represented in the automation station.

P1-Instance-Range

P1InstRng

P1 instance range

A read-only proprietary property that defines the range of instance numbers to be reserved in the automation station for the P1 device.

P1-Application

P1Appl

P1 application

This property can only be written once. Once the application number is set to a non-zero value, the user must delete and re-add the Peripheral Device Object.

Panel-Initial-Value-Block

pnlInitValBlk

Panel initial value block

A read-only proprietary property that is the PXC.A image of the initial values for a P1 device.

Device-Services

DevServ

Device Services

A writable proprietary enumerated trigger property used to issue various commands to device services:

  • Get Initial Values. Get the initial values from the P1 TEC and store them in the PXC.A device.
  • Set Initial Values. Clear the Initial Values at the P1 TEC and send the initial values stored in the PXC.A device.
  • Clear Initial Values. Clear the initial values at the P1 TEC and any values stored in the PXC.A.
  • Reboot. Restart the device.