The automation station point team appears in the My device collection. My device collection members are generated by firmware and cannot be deleted or renamed. The collection members are described in the following table.
Object Name | Object Profile | Description |
---|---|---|
AlmCnt | Apogee-Aggregation-By-Ref-Obj | The count of objects in the local device that have an offnormal state, Status_Flags = IN_ALARM. This also includes objects with an array of references to the objects in the local device that have an offnormal state. |
OosCnt | Apogee-Aggregation-By-Ref-Obj | The count of objects in the local device that are out-of-service, Status_Flags = OUT_OF_SERVICE. This also includes an array of references to the objects in the local device that are out-of-service. |
UnAckCnt | Apogee-Aggregation-By-Ref-Obj | The count of objects in the local device that have one or more unacknowledged event state transitions; objects with one or more cleared Acked_Transition, This includes an array of references to the objects in the local device with unacknowledged event state transitions. |
FaultCnt | Apogee-Aggregation-By-Ref-Obj | The count of objects in the local device that are in fault state, Status_Flags = FAULT. This inclues an array of references to the objects in the local device that are in fault state. |
CmdCnt | Apogee-Aggregation-By-Ref-Obj | The count of objects in the local device that are commanded; objects with a non-null value in any of the priority-array slots 1-8, including an array of references to the objects in the local device that are commanded. |
Holiday | BA_BinaryCalculatedValue | True if the current day appears in a PPCL Holiday() statement in the local device, otherwise False. The Holiday() PPCL statement and the Holiday object are provided for backward compatibility with existing programs and should not be used on new projects. On new projects, the present-value of one or more Calendar objects should be used to determine whether the current day is a holiday. |
BnPollCycleDiag | BA_Diagnostics | The count of objects in the local device that are polling at a given rate. |