BACnet Property

Short Name

BACnet Description

Notes

object-type

ObjTyp

Object type

BACnet object NC. The Notification class replaces the Desigo destination.

notification-class

NotifCl

Notification class

A read-only standard BACnet property that specifies the unique numeric identifier for the object's notification class. The value of Notification-Class is equal to the Notification-Class object instance number.

ack-required

AckReq

Acknowledgement required

A writable standard BACnet property with three flags indicating which alarm transitions require operator acknowledgement.
{to-offnormal, to-fault, to-normal}

priority

Prio

Priority

A writable standard BACnet property that specifies the alarm priorities for each type of alarm transition.
{to-offnormal prio, to-fault prio, to-normal prio}

recipient-list

RecpList

Recipient list

Each BACnetDestination structure includes an identifier for the client device, optional filters based on time of day, day of week, and active alarm state, along with other parameters.