These properties are only available when Subsystem is set to BO-PULSE.
BACnet Property | Short name | BACnet Description | Notes |
---|---|---|---|
Pulse-Time | TiPls | Pulse time | A writable proprietary property that specifies the output pulse length, in tenths of a second. |
Break-Time | DlySwovr | Switchover delay | A writable proprietary property that specifies the minimum break time between on and off pulses, in tenths of a second. |
COV-Repetition-Timer | TiExcgRptCl | COV repetition time | A writable proprietary enumerated property that configures the time interval between value updates from the Output object to data acquisition. Data acquisition will be updated even if the value does not change. COV-Repetition-Timer is not used for onboard IO and is ignored. |