These properties are only available when Subsystem is set to BI-SWITCH-IO.
BACnet Property | Short name | BACnet Description | Notes |
---|---|---|---|
Allowed-Signal-Types | SigTypSprtd | Supported signal types | A read-only proprietary property that specifies a selectable set of sensor types for the input. |
Signal-Type | SigTyp | Signal type | The subset of supported signal types is HW specific and depends on the Allowed-Signal-Types property. |
Signal-LED | LEDActvInd | LED active indication | A writable proprietary enumerated property that specifies the LED color to be used when the physical input value is active. |
COV-Repetition-Timer | TiExcgRptCl | COV repetition time | A writable proprietary enumerated property that configures the time interval between data acquisition COVs to the Input object. Data acquisition COVs will be sent at this interval even if the raw sensor value does not change. The enumeration range for COV-Repetition-Timer is {T1, T2, T3}, where T1 is the shortest interval and T3 is the longest. |