These properties are only available when Subsystem is set to POS (positioning).
BACnet Property | Short name | BACnet Description | Notes |
---|---|---|---|
Allowed-Signal-Types | SigTypSprtd | Supported signal types | A read-only proprietary property that specifies a selectable set of physical actuated output types. Supported signals: |
Signal-Type | Signal-Type | SigTyp | A writable proprietary enumerated property that specifies the physical actuated output type selected for the Analog-Output object instance. The enumeration range corresponds to the Allowed-Signal-Types. |
Present-Value-1 | PrcVal1 | Process value 1 | A writable proprietary property that specifies the scaled output value, in engineering units, that corresponds to the physical output value, Signal-Value-1. |
Signal-Value-1 | SigVal1 | Signal value 1 | A writable proprietary property that specifies a raw unscaled physical output value used to define the two-point sensed value conversion equation. A two-point method is used rather than the slope-intercept method. |
Present-Value-2 | PrcVal2 | Process value 2 | A writable proprietary property that specifies the scaled output value, in engineering units, that corresponds to the physical output value, Signal-Value-2. |
Signal-Value-2 | PrcVal2 | Signal value 2 | A writable proprietary property that specifies a second raw unscaled physical output value used to define the two-point sensed value conversion equation. A two-point method is used rather than the slope-intercept method. |
COV-Repetition-Timer | TiExcgRptCl | COV repetition time | A writable proprietary enumerated property that configures the time interval between value updates from the Output object to data acquisition . Data acquisition will be updated even if the Output value does not change. |