These properties are only available when Subsystem is set to POS (positioning).

BACnet Property

Short name

BACnet Description

Notes

Allowed-Signal-Types

SigTypSprtd

Supported signal types

A read-only proprietary property that specifies a selectable set of physical actuated output types. Supported signals:
U10, I420

Signal-Type

Signal-Type

SigTyp

A writable proprietary enumerated property that specifies the physical actuated output type selected for the Analog-Output object instance.

The enumeration range corresponds to the Allowed-Signal-Types.

Present-Value-1

PrcVal1

Process value 1

A writable proprietary property that specifies the scaled output value, in engineering units, that corresponds to the physical output value, Signal-Value-1.

Signal-Value-1

SigVal1

Signal value 1

A writable proprietary property that specifies a raw unscaled physical output value used to define the two-point sensed value conversion equation. A two-point method is used rather than the slope-intercept method.

Present-Value-2

PrcVal2

Process value 2

A writable proprietary property that specifies the scaled output value, in engineering units, that corresponds to the physical output value, Signal-Value-2.

Signal-Value-2

PrcVal2

Signal value 2

A writable proprietary property that specifies a second raw unscaled physical output value used to define the two-point sensed value conversion equation. A two-point method is used rather than the slope-intercept method.

COV-Repetition-Timer

TiExcgRptCl

COV repetition time

A writable proprietary enumerated property that configures the time interval between value updates from the Output object to data acquisition . Data acquisition will be updated even if the Output value does not change.