Foreign Device Extensions
BACnet Property | Short Name | BACnet Description | Notes |
---|---|---|---|
BACnet-IP-Mode | BnIpMod | IP mode | A writable proprietary enumerated property that specifies whether the device acts as a foreign device on the BACnet IP network. The range of values for BACnet-IP-Mode is: {normal, foreign}. |
FD-BBMD-Address | FdBbmdAddr | Foreign device BBMD address | A writable proprietary property that specifies the BBMD to which the local device will register as a foreign device. |
FD-Subscription-Lifetime | FdSbcLifeTi | Foreign device subscription lifetime | A writable proprietary property that specifies the Time-To-Live value, in seconds, to be used in the Register-Foreign-Device BVLL message. |
BBMD Foreign Device Extensions
NOTE:
Checking Enable BBMD in ABT Site makes IP Mode editable. It does not automatically make the device a BBMD.
BACnet Property | Short Name | BACnet Description | Notes |
---|---|---|---|
BACnet-IP-Mode | BnIpMod | IP mode | A writable proprietary enumerated property that specifies whether the device acts as a foreign device on the BACnet IP network. The range of values for BACnet-IP-Mode is: {Normal, Foreign, BBMD}. |
BBMD-Broadcast-Distribution-Table | BbmdBdt | BBMD broadcast distribution table | A writable proprietary property that specifies the broadcast distribution table entries for a device configured as a BBMD. Applies only if IP Mode is set to BBMD. If IP Mode is not set to BBMD, the BBMD-Broadcast-Distribution-Table property shall be read-only and empty. |
BBMD-Accept-FD-Registrations | BbmdAcptFd | BBMD accept FD registrations | A writable proprietary property that specifies whether this device will accept foreign device registrations. Applies only if IP Mode is set to BBMD. If IP Mode is not set to BBMD, the BBMD-Accept-FD-Registrations property shall be read-only and No. |
BBMD-Foreign-Device-Table | BbmdBdt | BBMD broadcast distribution table | A read-only proprietary property that specifies the foreign device table entries for the BBMD-enabled device. BBMD-Foreign-Device-Table shall be read-only and empty if BACnet-IP-Mode is not set to BBMD. |
FD-BBMD-Address | FdBbmdAddr | Foreign device BBMD address | A writable proprietary property that specifies the BBMD to which the local device will register as a foreign device. FD-BBMD-Address shall be read-only and empty if BACnet-IP-Mode is not set to foreign. |
FD-Subscription-Lifetime | FdBbmdAddr | Foreign device BBMD address | A writable proprietary property that specifies the Time-To-Live value, in seconds, to be used in the Register-Foreign-Device BVLL message. FD-Subscription-Lifetime shall be unused and read-only if BACnet-IP-Mode is not set to foreign. |