BACnet Property

Short Name

BACnet Description

Notes

object-type

ObjTyp

Object type

Value: 2 (analog-value)

profile-name

PrfNam

Profile name

Value: 7-333-SBCv15.03

Prototype

BAObjTyp

Building automation profile

Value: 333 (AnalogSimpleProcessValue)

present-value

PrVal

Present value

A writable standard BACnet property that indicates the current analog value, in engineering units.

Startup-Default

StupDef

Startup default

A writable proprietary property that specifies the initial value of the present-value property at startup, in engineering units.

units

Un

Units

A writable standard BACnet enumerated property that indicates the measurement units of this object.

resolution

Rsl

Resolution

A writable standard BACnet property that specifies indicates the smallest recognizable change in present-value in engineering units.

max-pres-value

PrValMax

Present maximum value

A writable standard BACnet property that indicates the highest number in engineering units that can be reliably obtained for the present-value property of this object.

min-pres-value

PrValMin

Present minimum value

A writable standard BACnet property that indicates the lowest number in engineering units that can be reliably obtained for the present-value property of this object.

cov-increment

Cov

Change of value, COV

A writable standard BACnet property that specifies the minimum change in present-value that will cause a COV Notification to be issued to subscriber COV-clients.

Alarm-Extension

AlarmExtn

Event configuration

A writable enumerated proprietary property that specifies whether the optional intrinsic alarming extension is enabled for the object.

Aggregation-Extension

AggtnExtn

Aggregation: Operating hours & others

A writable enumerated proprietary property that allows an optional aggregation extension to be enabled for the object.