BACnet objects represented by physical I/O points.

Property Name

Description

device-type

A writable standard BACnet property may be used to provide a textual description of the physical device represented by the object. Device-type will typically indicate the type and/or part number of the peripheral device.

IO-Extension

A writable enumerated proprietary property that specifies the type of IO extension used by this Object. .

IO-Address

A writable proprietary property that specifies the fieldbus (e.g. IO-0 for Onboard-I/O, IO-1 for TX-I/O) and IO module that this object represents.

Commissioning-State

A writable proprietary enumerated property, that indicates whether the object and its associated IO have been checked out during the commissioning process.

Commissioning-Info

A writable proprietary property that provides additional textual commissioning information about the Object.