The PXC.A sends alarm messages to the recipient list (destinations) in the associated notification class if the following conditions are met:

  • the alarm is enabled for Offnormal events
  • the destination is enabled for Offnormal events
  • the destination is active based on day of week and time of day
  • the automation station status is Ready in the node table

The PXC.A sends normal messages to the recipient list in the associated notification class if the following conditions are met:

  • the alarm enabled for Normal events
  • the destination is enabled for Normal events
  • the destination is active based on day of week and time of day
  • the automation station status is Ready in the node table

The PXC.A sends fault messages to the recipient list in the associated notification class if the following conditions are met:

  • the alarm is enabled for Fault events
  • the destination is enabled for Fault events
  • the destination is active based on day of week and time of day
  • the automation station status is Ready in the node table

 

NOTE:
When creating a Notification class ensure the first recipient has a valid day selected. Any other recipient in the list is deleted if the first recipient is not defined properly.