BACnet Property | Short Name | BACnet Description | Notes |
---|---|---|---|
object-type | ObjTyp | Object type | Value: 5 (binary-value) |
profile-name | PrfNam | Profile name | Value: 7-334-SBCv15.03 |
Prototype | BAObjTyp | Building automation profile | 334: (BinarySimpleProcessValue) |
present-value | PrVal | Present value | indicates the current logical value. The enumeration range for BACnetBinaryPV is {INACTIVE, ACTIVE}. |
Startup-Default | StupDef | Startup default | specifies the initial value of the present-value property at startup. The enumeration range for BACnetBinaryPV is {INACTIVE, ACTIVE}. |
inactive-text | IactvTxt | Inactive text | specifies a human-readable description of the INACTIVE state. |
active-text | ActvTxt | Active text | specifies a human-readable description of the ACTIVE state. |
Alarm-Extension | AlarmExtn | Event configuration | A writable enumerated proprietary property that specifies whether the optional intrinsic alarming extension is enabled for the object. |