To perform a direct factory reset:

  1. Remove power from the CFG3.F200
  1. Press and hold the SVC button. While holding:
  • Apply power to the CFG3.F200. The device will default to a blinking red SVC light.
  • Continue holding the SVC button.

In approximately 30 seconds, a steady green RUN light will turn on.

  • Release the SVC button

The device will now reboot and enter an unconfigured mode, signified by a red blinking light. Press/double press the SVC button to change the device's IP to 169.254.169.254.