Once you have ensured cloud connectivity and updated the latest gateway application software to the F200 device, you must next configure the firewall rules. By default, inbound traffic is not allowed on the device. You must open the ports so the F200 device can communicate with the building automation network.
The Desigo Optic operating system must finish updating before you configure the firewall rules in the device (as outlined in the section above).
To manually configure the F200:
- Select the Network tab. Then, select the Firewall header.
- Create the following inbound rules for:
Separate Network Mode
Description | Protocol | Source Port |
---|---|---|
BACnet IP devices | udp | 47808 |
Desigo Optic Web-client | tcp | 8090 (HTTPS) |
Default | All rejected |
|
Single Network Mode
Description | Protocol | Source Port |
---|---|---|
BACnet IP devices | udp | 47808 |
Desigo Optic Web-client | tcp | 8090 (HTTPS) |
Default | All rejected |
|
Requirements for Horizon (Devices)
Description | Protocol | Source Port |
---|---|---|
HTTPS | tcp | 443 |
MQTTS | tcp | 443 |
NTP | udp | 123 |
Depending on building automation network configuration on site, the source ports may differ.
- Click Edit to change the port.