Before using Desigo Optic, you need to create a site, add and activate your device, and update your device in Device Manager.

  1. Use the following link to access Device Manager: https://assets.bpcloudapps.siemens.com/#/login
  1. Log in using your credentials.

 

NOTICE
If you do not have access to Device Manager through the above link, please process order form FIN-CLOUD-OPTIC.

Creating a site

  • In Devices:
  1. Create a new site via one of the options below:
  • Go to Dashboard > New site.
  • Go to Sites > Add.
  1. Fill in the fields on the Add site form.
  1. Select Add.

The Address field will automatically suggest addresses. Selecting a suggested address will automatically populate the Time Zone field. If Google API is unavailable, you will need to enter in an address and time zone manually.

Adding and activating device

  • After adding a site, in Devices:
  1. Go to Sites.
  1. Select the site where you want to add your device.
  1. Select Add.
  1. Enter the device activation key and select Validate.

For F200 devices, the activation key is available in the Operation tab of the Config UI.

  1. Confirm the details of your device.
  1. Select Add.

 

When defining or changing the custom name of the device, it will only affect the display name in the cloud. Leave the Custom name and Custom description fields blank.

ModBus RTU Devices

By supporting RS-485 connectors (also known as EIA/TIA-485 connectors), the CFG3.F200 provides bidirectional communication between multiple devices mirrored along two alternating main wires, which reduces electromagnetic interference, preserves data integrity, and allows for the setup of a long-distance multi-device serial network with more than one transmitter and receiver.

Users may assign a RTU device following the Modbus protocol directly to COM1 or COM2. The RS-485 connector will enable users to read and write points from Desigo Optic.

Setup

 

Assigning distributions

After adding and activating the device, assign the distribution to enable Desigo Optic Discovery. To assign a distribution to the device, follow the steps below:

Assigning a distribution set will only need to be done once. The assign distribution pop-up will only appear after adding a device in a site. If you do not assign a distribution, this pop-up will appear until the device is assigned a distribution.

  • In Devices:
  1. Go to Sites.
  1. Select the site with the F200 device.
  1. Select the device.
  1. Go to Applications.
  1. In the pop-up, use the drop-down menus to Select distribution and Select distribution version.
    NOTE: Verify that the latest distribution version is selected.
  1. Select Save.

Updating distributions

To update a distribution on a device, follow the steps below.

  • In Devices:
  1. In the Sites tab, select the site with the F200 device.
  1. Select the device.
  1. Go to Applications.
  1. To update the distribution, select Update.
  1. Confirm with Update.
  1. Desigo Optic is not installed by default. To install Desigo Optic, select Install > Synchronize. To monitor progress, navigate to Network IP Setting. There, the LAN graph displays all download activity.
  1. Navigate to the Services tab and find the status of your application. The controller is ready to be used when the application displays as Running and healthy in the Services tab. If download time exceeds five minutes, navigate back to Applications and press Synchronize again.

Update Operating System

To update the operating system of the Connect device, follow the steps below.

  • In Devices:
  1. Go to Sites.
  1. Select the site with the F200 device.
  1. Select the device > Updates.
  1. Select Update
  1. Confirm with Update.

The operating system update could take approximately 20 minutes depending on your network bandwidth. Ensure that the download rate of your network bandwidth is at least 8Mbit/second, or else the update will likely time out. Wait before proceeding to the next step.

If you update the operating system, you’ll be logged out of the F200 Device Interface.

  • (Optional) In F200 device:
  • Go to the Maintenance tab in Desigo Optic to follow the software update in real-time.