Although the global unbundler selects subpoints for all TEC device objects with the same application number, they must be cleared from each TEC peripheral device object. Global subpoints that have been removed with the global unbundler remain selected with the selective unbundler. To clear a subpoint from both unbundlers, clear the subpoint from the global unbundler first, and then clear it from the selective unbundler.

Clearing global subpoints

  1. Go to Object view > Field bus.
  1. Expand the P1 Fln view node.
  1. Click on a TEC peripheral device object. In the object management area, the application team displays first in the list.
  • To clear selections made in properties, proceed to Step 4.
  • To clear selections made in the subpoint unbundle editor, proceed to Step 5.
  1. Click on the application team.
  • Click Global unbundle.
  • Click on an unbundled subpoint and clear the text field.
  • Click to save.
  • The subpoint has been cleared from the global unbundler. Subpoints that are still selected in the selective unbundler will continue to display in the object management area.
  1. Click on the application team.
  • Uncheck a box to clear the subpoint from the subpoint unbundle editor.
  • Click Save to save.
  • The subpoint has been cleared from the global unbundler. Subpoints that are still selected in the selective unbundler will continue to display in the object management area.