The Buffer size property can be written to modify the memory size of a trend log object.

  • The Enable logging property is set to No.
  1. Open the properties of the trend log object that requires its buffer size to be rewritten.
  1. Ensure the Notification threshold property is less than or equal to the desired buffer size.
  • Modify the Notification threshold property as necessary.
    NOTE: The buffer size cannot be rewritten if the value Notification threshold property is less than the value of the buffer size.
  • Click to save.
  1. Write the Buffer size to the new value.
  • Click to save.
  1. Set the Enable logging property back to Yes.