Setting the Event configuration property to Change of state enables the Change of state extension. This extension detects whether a binary object property is equal to a configured alarm value or an enumerated property is equal to one of a configured set of alarm values. The Change of state extension can be applied to Binary_Input
, Binary_Output
, Binary_Value
, Multistate_Input
, Multistate_Output
, and Multistate_Value
objects.
Selecting the Change of state extension enables the property outlined in this table.
Property name | Description |
---|---|
Property state values count | Sets the size of the Property state values array. |
Property state values | Determines the alarm value(s) for the extension. |
Time delay | Specifies the amount of time that must pass between detecting offnormal conditions and sending an event notification. Enter a time in seconds. |